Online UPS 15KVA to 20KVA

Universe: UPS
Subrange: UPS

The UKN Online UPS 15–20 kVA range connects to a three-phase 380 / 400 / 415 Vac supply and delivers a single-phase output. The load is spread evenly across the three phases of the installation, which suits data rooms, high-density cabinets, healthcare sites and production equipment.

Online double conversion with DSP control and 3-level technology provides a pure sine wave, a voltage distortion of 1% or less on linear loads and a transfer time of 0 ms. The output power factor of 1.0 makes the full rating available in kW. Efficiency is 94% at full load, peaks at 95% at 60% load and reaches 98% in ECO mode.

The input window is wide, from 190 to 478 Vac and 40 to 70 Hz, with a power factor up to 0.99. The UPS works with an external battery string of 16 to 20 blocks, sized to the runtime required, and its digitally controlled charger delivers up to 10 A as an option. Up to four units can be paralleled for capacity or redundancy.

The 3U chassis is 440 mm wide and 780 mm deep. RS232 and a smart card slot are standard; SNMP, USB, RS485, dry contacts, environmental monitoring, battery temperature compensation and SMS alarms are options.

Unik

  • Three-phase input, single-phase output: balanced load on the mains
  • Output power factor 1.0: 15 kVA = 15 kW, 20 kVA = 20 kW
  • Efficiency ≥ 94% at full load, up to 98% in ECO mode
  • Parallel operation up to 4 units, external battery string of 16 to 20 blocks

Datasheets & Docs

  • KCFF6AxPZHD

  • Lorem ipsum dolor sit amet, consectetur adipiscing elit

  • Lorem ipsum dolor sit amet, consectetur adipiscing elit

  • KCFF6AxPZHD

  • KCFF6AxPZHD

  • Lorem ipsum dolor sit amet, consectetur adipiscing elit

  • Lorem ipsum dolor sit amet, consectetur adipiscing elit

  • KCFF6AxPZHD

Specs

Dive into technicalities

  • Capacity15 kVA / 15 kW · 20 kVA / 20 kW
    TopologyOnline double conversion, high frequency
    InputThree-phase (3Φ + N + PE), 380 / 400 / 415 Vac
    Input voltage range190–478 Vac (304–478 Vac without derating)
    Input frequency50 / 60 Hz auto-sensing, range 40–70 Hz
    Input power factor≥ 0.99
    Input THDi≤ 5 %
    Bypass voltage range−40 % to +15 % (settable)
    OutputSingle-phase (L-N), 208 / 220 / 230 / 240 Vac ± 1 %
    Output frequencySynchronized to bypass in mains mode; 50 / 60 Hz ± 0.1 % in battery mode
    WaveformPure sine wave
    Output power factor1.0
    Output THDv≤ 1 % (linear load), ≤ 3 % (non-linear load)
    Crest factor3:1
    Overload105–110 % for 10 min, 110–125 % for 1 min, 126–150 % for 30 s
    BatteryExternal, 192 Vdc (192–240 Vdc settable), 16 blocks (16–20 settable)
    Charging current5 A default, 1–5 A settable, 10 A optional
    Efficiency≥ 94 % at 100 % load, max. 95 % at 60 % load, ≥ 98 % in ECO mode
    Transfer time0 ms
    Parallel operationUp to 4 units
    ProtectionsShort-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage, fan failure
    CommunicationsRS232 (standard); USB, RS485, dry contacts, SNMP, battery temperature compensation (optional)
    DisplayLCD + LED
    Operating temperature0 °C to 40 °C
    Relative humidity0–95 % (non-condensing)
    Altitude≤ 1000 m, derating 1 % per additional 100 m
    IP ratingIP20
    Noise level at 1 m≤ 58 dB
    Dimensions W × D × H440 × 780 × 132 mm (3U)
    Net weight25.5 kg (without batteries)

Ordering information

Navigate purchase info

    • Item
    • KUPS20K15K192
    • KUPS20K20K192
    • Designation
    • Online UPS 15KVA
    • Online UPS 20KVA
    • Capacity / Power
    • 15KVA / 15 000 W
    • 20KVA / 20 000W
    • Packing
    • 1 Pc
    • 1 Pc