| Capacity | 1 kVA / 2 kVA / 3 kVA |
|---|---|
| Topology | Online double conversion, high frequency |
| Input | Single-phase, 208 / 220 / 230 / 240 Vac |
| Input voltage range | 110–300 Vac (176–280 Vac without derating) |
| Input frequency | 40–70 Hz (auto-sensing) |
| Input power factor | ≥ 0.99 |
| Input THDi | ≤ 6 % |
| Output voltage | 208 / 220 / 230 / 240 Vac ± 1 % (settable via LCD) |
| Output frequency | 50 / 60 Hz ± 0.1 Hz in battery mode |
| Waveform | Pure sine wave |
| Output power factor | 0.9 / 1.0 |
| Output THDv | ≤ 2 % (linear load), ≤ 5 % (non-linear load) |
| Crest factor | 3:1 |
| Overload | 105–125 % for 1 min, 125–150 % for 30 s, > 150 % for 300 ms |
| Transfer time | 0 ms mains to battery; 4 ms typical inverter to bypass |
| Efficiency, mains mode | ≥ 90 % (1 kVA), ≥ 91 % (2 kVA), ≥ 92 % (3 kVA) |
| Efficiency, ECO mode | ≥ 95 % (1 kVA), ≥ 96 % (2 kVA), ≥ 97 % (3 kVA) |
| Charging current | 1 A (standard model), 6 A (long-time model) |
| Recharge time | 90 % in 3 h (standard model) |
| Protections | Short-circuit, overload, overtemperature, battery discharge, fan fault |
| Communications | RS232 (standard); USB, RS485, dry contacts, SNMP (optional) |
| Display | LCD + LED |
| Standards | EN/IEC 62040-1, EN/IEC 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2/-3/-4/-5/-6/-8/-11, IEC 61000-2-2 |
| Operating temperature | 0 °C to 40 °C |
| Relative humidity | 0–95 % (non-condensing) |
| Altitude | ≤ 1000 m, derating 1 % per additional 100 m |
| IP rating | IP20 |
| Noise level at 1 m | ≤ 50 dB |
| Format | 19-inch rack/tower, 2U (W 440 × H 88 mm), depth 338 to 560 mm depending on version |
| Net weight | 7.6 to 26.8 kg depending on version |